Complete fuel gas conditioning trains for combined-cycle and cogeneration plants: filter-coalescer, gas heater, fiscal measurement, pressure reduction, and ESD — sized for Siemens, GE, and MAN turbines.
We design fuel gas preparation trains for the specific turbine: ensuring the required superheat, cleanliness, and pressure stability of the fuel at the GT inlet.
ESD and F&G logic fully tested at FAT, HAZOP-cleared documentation, ready for EPC integration.
Double block-and-bleed, filter-coalescer to 99.98 % at 0.3 µm, slam-shut on low pressure.
Ultrasonic meter with EVC and redundant pressure / temperature — AGA-9 compliant, ± 0.5 % class.
Monitor/active regulation + electric or water-glycol superheat to +20 K above dew point.
SIL-rated ESD valve, F&G detection, 2oo3 voting, MOC per IEC 61511 — signed off in FAT.